Secondary load resistance reflects back into the primary current budget, so lower load resistance demands more primary-side current. The 12, 6, and 3 ohm loads give primary load currents 1/4, 1/2, and 1 A against a 1/2 A budget exactly for the ideal turn-ratio model; real transformers add winding resistance, leakage inductance, regulation, core loss, heating, parasitic capacitance, load variation, and current measurement uncertainty.
Secondary load resistance becomes a primary-side current budget. Exact arithmetic here means exact results for the stated model inputs; measured inputs still carry uncertainty and significant-figure limits.
highlighted = computed this step
Load resistance row 1
Transformer voltage ratio stays fixed. Secondary load 12 ohm gives secondary current 1/2 A and primary load current 1/4 A against a 1/2 A budget, so margin is 1/4 A.
m=41Apass
Load resistance row 2
Transformer voltage ratio stays fixed. Secondary load 6 ohm gives secondary current 1 A and primary load current 1/2 A against a 1/2 A budget, so margin is 0 A.
m=0Apass
Load resistance row 3
Transformer voltage ratio stays fixed. Secondary load 3 ohm gives secondary current 2 A and primary load current 1 A against a 1/2 A budget, so margin is negative 1/2 A.